Surge protection devices Lovato 3x+Ν Type 1 & 2 with plug-in cartridge

Surge protection devices Lovato 3x+Ν Type 1 & 2 with plug-in cartridge
Product Inquiry

Product Inquiry

Surge protection devices Lovato 3x+Ν Type 1 & 2 with plug-in cartridge

    DETAILED DESCRIPTION

    The surge arresters commonly defined as SPDs (Surge Protection Devices), are devices designed to protect electric systems and equipment against transient and impulse overvoltages such as those caused by lightning and by electric switching.
    Their function is to divert the discharge or impulse current generated by an overvoltage to earth/ground, thereby protecting the equipment downstream. SPDs are installed in parallel with the electric line to be protected. At the mains rated voltage, they are comparable to an open circuit and have a high impedance at their ends.
    In the presence of an overvoltage, this impedance falls to very low values, closing the circuit to earth/ground.
    Once the overvoltage has ended, their impedance rises again rapidly to the initial value (very high), returning to open loop conditions.
    The SA1B (monoblock) type protects against direct and indirect lightning strikes as well as induced overvoltage conditions. It can be installed in areas with a high risk of direct lightning strikes, inside main distribution boards or nearby sub-distribution boards.

    Protection zones

    Standards define the LPZs (Lightning Protection Zones), which indicate the different zones at risk. These are distinguished among:
    LPZ 0A: Area outside a building not protected by LPS (e.g. lightning rods) where a direct lightning strike is possible. In this zone, there is total exposure to induced electromagnetic fields.
    LPZ 0B: Area outside a building protected by LPS; therefore, a direct lighting strike is not possible. In this zone, there is total exposure to induced electromagnetic fields.
    LPZ 1: Area inside a building so protected against direct lightning strikes. In this zone, there is the possibility of very high overvoltages and of induced electromagnetic fields which may be attenuated depending on the degree of screening. This zone must be protected by an SPD type 1 at the boundary with zone LPZ 0A or 0B.
    LPZ 2: Area inside a building (e.g. in a room), in which there is the possibility of low overvoltages since they are limited by SPDs installed upstream. This zone must be protected by an SPD type 2 at the boundary with zone LPZ 1.
    LPZ 3: Area inside a building (e.g. the system connected to a socket in a room) characterised by very sensitive equipment, in which there is the possibility of very low overvoltages as they are limited by SPDs installed upstream.
    This zone must be protected by an SPD type 3 at the boundary with zone LPZ 2.

    Comply with standards: IEC/EN 61643-11.

    Further information about these products and their accessories at pdf-link below.

    • Ονομαστική Τάση (Un)
      230/400 V
    • Voltage protection level (Up) L-N
      <1.5 kV
    • Power installation system
      TT, TN-S
    • Poles
      3x+N
    • Relay Output
      Yes
    • LPZ
      1, 2