We use cookies to provide you with a top-notch browsing experience. You can find more information about cookies here. By selecting "Accept Cookies" you accept their placement.

Learn more

765-2701/200-000, analog, converter, mA, transducer
1-channel analog input. IO Link Converter. 4-20 mA. 2 x M12 connection. WAGO

Product Inquiry

Product Inquiry

1-channel analog input. IO Link Converter. 4-20 mA. 2 x M12 connection. WAGO

    DETAILED DESCRIPTION

    765-2701/200-000

    1-channel analog input; IO Link Converter; 4 … 20 mA; 2xM12 connection

    Application:

    Decentralized display, preprocessing and conversion of analog signals

    Use as an IO-Link device:

    The device has an IO-Link communication interface that requires an IO-Link-capable module (IO-Link master) for interoperation.

    The IO-Link interface allows direct access to the process and diagnostic data and enables setting of the device parameters during operation.

    Use as a stand-alone device without IO-Link:

    The device compares the measured current value with the set parameters and switches the output according to the selected function.

    This mode is without IO-Link functionality. Parameterization is performed either via the push ring or with the WAGO IO-Link Configurator.

     

    Technical data

    Communication:    IO-Link Class A

    IO-Link version:    1.1

    Digital outputs: 1

    Analog inputs: 1

    Analog outputs: 1

    Signal type: Current= 4 … 20 mA, Voltage= 10 … 30 VDC

    Output circuit: Make/break contact; parameterizable

    Operating mode:   SIO; IO-Link

    Transmission modes:          COM2 (38.4 kBaud)

    Parameterizable functions: Operating mode, switching point, delay, scaling, etc.

    Accuracy (+25 °C): 0,5 %

    Cycle time: 3.2 ms (min.)

    Supply voltage: 24 VDC (18 … 30 V)

    Process data: 1 x 16 Bit IN (analog); 1 x 16 Bit IN (digital)

    Indicators: Digital output (1 x yellow LED), Power (1 x green LED), Display (7-segment red/green LED

     

    Connection technology

    Inputs/outputs: 1 x M12-A socket 5-pole (inputs), 1 x M12-A plug 4-pole (outputs, IO-Link)

     

    Environmental requirements

    Ambient temperature (operation): -20 … +60 °C (70 °C with display switched off)

    Ambient temperature (storage): -25 … +70 °C

    Protection type: IP67

    Pollution degree: 3

    Operating altitude: 0 … 2000 m

     

    Other models:

    1-Channel Analog Input; IO-Link Converter; 4 … 20 mA Code: 765-2701/200-000 38

    2-Channel Analog Input; IO-Link Converter; 0 … 10 V Code: 765-2702/200-000 39

    2-Channel Analog Output; IO-Link Converter; 4 … 20 mA Code: 765-2703/200-000 40

    2-Channel Analog Output; IO-Link Converter; 0 … 10 V Code: 765-2704/200-000 41

    1-Channel Analog Input; IO-Link Converter; Pt100/Pt1000; voltage Code: 765-2705/200-000 42

    1-Channel Analog Input; IO-Link Converter; Pt100/Pt1000; current Code: 765-2706/200-000 42

    Mounting Clip 765-101/000-000, Code: 765-102/000-000 4

     

    DOCUMENTS AND SPECIFICATIONS